P-3835 Toluene gas detector is designed to detect Toluene in industrial areas. ATEX, IECEx certified P-3835 is ready to use in an explosive atmosphere.
Pellistor sensor in P-3835 shows the excellent result in 0-100%LEL
Connectivity
• Sensor: Uses high-quality Pellistor sensor specially designed to detect Toluene
• Modbus: It is easy to integrate SCADA systems via open-source Modbus RS485(RTU) codes
• Outputs: Different devices can be operated/controlled at the same time thanks to the 4-20mA analog, Modbus RS485, and Relay outputs
• Relay Contacts: P-3R+ relay module integrated P Series detectors can manage other equipment or it can be linked to firefighting panels.
Maintenance and Installation
• Sensor Replacement: Allows sensor replacement with pre-calibrated sensor head to provide easy maintenance.
• Installation: Designed for either wall or ceiling mounting applications
• Entry: 2 x 1/2″ NPT cable entries
• Remote Control: Detector status can be also monitored via Prosense Gas Monitoring software remotely.
Robust and Reliable
• Body: Aluminium die-cast body and SS316 stainless steel sensor head superb performance under harsh environmental conditions with IP65 protection class.
Sensor Technology | Pellistor |
Output Signal | 4-20mA and Modbus RS485 RTU |
Sensor Warm-Up | 60sec |
Response Time(T90) | <20sec |
Accuracy | %±1 |
Operating Temperature | -40°C ~ +70°C |
Humidity | 5 ~ 95%RH |
Input | Min 10VDC - Max 32VDC - Nominal 24VDC |
Power Consumption | Max. 4W |
Relay Outputs | 2 Alarms (Selectable) and 1 Fault (All relays are NO/NC adjustable) |
IP Rating | IP65 / IP66 |
Junction Box | Epoxy Painted Die-Cast Aluminum |
Sensor Head | 316L Stainless Steel |
Dimensions/Weight | 183x118,15x88mm / 1420gr |
ATEX Marking | II 2G Ex db IIC T5/T4 Gb |
Hazardous Class | Zone 1 or Zone 2 |
Certificates | IMQ 19 ATEX 045 X IECEx IMQ 18.0009X |
Standards | IEC EN 60079-0 IEC EN 60079-1 IEC EN 60079-18 |
Önerilen Ürünler
P Series Datasheet
P Series User Manual