PE-KAYO Series specially designed for the Oil&Gas stations as it has multiple functions. The detector has a special accelerometer chip inside to monitor physical bumps happening on the location where the device installed along with gas measurement functions. It can generate an alarm to cut the gas and oil flow if a car or truck hits the detector or the mounted shaft. Moreover, the Catalytic sensor employed PE-Kayo for LPG gas shows excellent output in 0-100%LEL range.
• Sensor: Uses a high-quality catalytic sensor specially designed to detect LPG gas in 0-100%LEL and motion sensor to detect an impact.
• Certification: ATEX and IECEx certified PE Kayo-3012 is ready to use in an explosive atmosphere safely.
• Connection: Provides 4-20mA, Modbus RS485, and Voltage outputs
• Entry: 1 x 1/2″ NPT cable entry
• Body: Aluminium die-cast body and sensor head superb performance under harsh environmental conditions with IP65 protection class.
• Remote Control: Detector status can be also monitored via Prosense Gas Monitoring software remotely.
• Relay Contacts: With the P-3R+ relay module PE Kayo detectors can manage other equipment a siren, a beacon or can be linked into firefighting panels.
Certificates | IMQ 19 ATEX 045 X IECEx IMQ 18.0009X |
Standards | IEC EN 60079-0 IEC EN 60079-1 IEC EN 60079-18 |
Sensor Technology | Catalytic and Motion Sensor |
Output Signal | 4-20mA Analog, Modbus RS485 RTU and Voltage |
Sensor Warm-Up | 60sec |
Response Time(T90) | <15sec |
Accuracy | %±2 |
Operating Temperature | -40°C ~ +70°C |
Humidity | 5 ~ 95%RH Non-Condensing |
Input | Min 10VDC - Max 28VDC - Nominal 24VDC |
Power Consumption | Max. 4W |
Relay Outputs | 2 Relay Contacts (Alarm1-Fault or Alarm1-Alarm2) (All relays are NO/NC adjustable) |
IP Rating | IP65 |
Junction Box | Epoxy Painted Die-Cast Aluminum |
Sensor Head | Nickel‐Plated Brass |
Dimensions/Weight | 172,5x118,15x88mm / 1150gr |
ATEX Marking | II 2G Ex db IIC T4-T5 Gb |
Hazardous Class | Zone 1 or Zone 2 |
PE Series Datasheet
PE Series User Manual