ATEX/IECEx certified "PE" Series ex-proof gas detectors are designed and developed to detect explosive compounds in many applications as a cost-effective solution.
Catalytic sensors employed PE Series provide excellent output in 0-100%LEL.
Ask the Expert
• Sensor: Uses high-quality catalytic sensor specially designed to detect LPG, Methane, Petrol Vapour, Butane, Propane, and Hydrogen gases in 0-100%LEL.
• Certification: ATEX and IECEx certified PE Series ready to use in explosive atmosphere safely
• Connection: Provides universal standard 4-20mA analog output
• Entry: 1 x 1/2″ NPT cable entries
• Body: Aluminium die-cast body and sensor head superb performance under harsh environmental conditions with IP65 protection class.
• Remote Control: Detector status can be monitored Prosense Gas Monitoring software remotely.
• Relay Contacts: PE-2R+ relay module integrated PE Series detectors can manage other equipments or link to firefighting panels.
Sensor Technology | Catalytic |
Output Signal | 4-20mA Analog |
Accuracy | %1 |
Sensor Warm-Up | 60sec |
Operating Temperature | -40°C ~ +70°C |
Response Time(T90) | <15sec |
Humidity | 5 ~ 95%RH Non-Condensing |
Input | Min 10VDC - Max 28VDC - Nominal 24VDC |
Power Consumption | Max. 4W |
Relay Outputs | 2 Relay Contacts (Alarm1-Fault or Alarm1-Alarm2) |
IP Rating | IP65 |
Junction Box | Epoxy Painted Die-Cast Aluminum |
Sensor Head | Nickel-Plated Brass |
Dimensions/Weight | 172,5x118,15x88mm / 1150gr |
ATEX Marking | II 2G Ex db IIC T4-T5 Gb |
Hazardous Class | Zone 1 or Zone 2 |
Certificates | IMQ 19 ATEX 045 X IECEx IMQ 18.0009X |
Standards | IEC EN 60079-0 IEC EN 60079-1 IEC EN 60079-18 |